Final | 2/28/2018 | 3/1/2018 | 3/1/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
|
Final | 2/26/2018 | 2/27/2018 | 2/27/2018 | A | NR |
Brian Scoles
|
|
|
Also Blast witness. Will have them there set up and ready to blast at 9:30 Phone #: ###-#### Inspection requested via web by Randy Hart- needs line set hooked up- flue to water heater- line set uv taped outside and hole thru foundation closed off- not ready for final
|
Conference | 2/27/2018 | 2/27/2018 | 2/27/2018 | A | PASS |
Brian Scoles
|
|
|
Also Blast witness. Will have them there set up and ready to blast at 9:30 Phone #: ###-#### Inspection requested via web by Randy Hart- duct blast test pass- 97 cfm loss
|
Rough-in | 1/11/2018 | 1/12/2018 | 1/12/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- R/I ok- will need to witness duct blast test
|
Rough-in | 1/11/2018 | 1/11/2018 | 1/11/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- corrections not made- need crawl ducting complete for rough in inspection and dryer vent needs supported every 4 feet-
|
Rough-in | 1/9/2018 | 1/9/2018 | 1/9/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- dryer vent exhaust exceeds 35'/ reroute or add booster fan or show submittal of dryer being installed can handle the length- crawl needs complete to do inspection- need inert tape on gas line penetrating garage wall at meter location- left correction notice front window
|
Pressure Test | 1/9/2018 | 1/9/2018 | 1/9/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass
|