Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMEC18-00272
StatusFinaled
Name TML LLC
Site Address 1219 S BROADWAY AVE
Project NameAlbertsons
Customer Number22299-13
ePlanReviewNo
Description
New: HVAC
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/26/20187/27/20187/26/2018APASS
DetailsChad Schwendiman
Final inspection Contact Stan Lillquist ###-#### Pictures were emailed to Chad and Jack. Phone #: ###-#### Inspection requested via web by Dan Flaherty
Final7/24/20187/25/20187/25/2018AFAIL
DetailsChad Schwendiman
Final inspection, Contact Stan Lillquist ###-#### TAB report will email. Phone #: ###-#### Inspection requested via web by Dan Flaherty - Still need supports on the EVAP. section of the make up air units
Final6/21/20186/21/20186/21/2018PPART
DetailsChad Schwendiman
Final Inspection ; Antonio is your contact. Phone #: ###-#### Inspection requested via web by Kim Adams - Temporary occupancy okay. Need service protection rails in place on condensor with in 10' of the edge of the roof, Need grease trays installed on all grease fans, Need proper supports under evap sections of MUA's, Need completed air balance report.
Conference6/14/20186/14/20186/14/2018PPEND
DetailsBen Livingston
Conference ; Mike Beason is your contact. Phone #: ###-#### Inspection requested via web by Kim Adams
Rough-in6/11/20186/11/20186/11/2018PPASS
DetailsChad Schwendiman
rough in inspection ; Antonio is your contact. Phone #: ###-#### Inspection requested via web by Kim Adams - bakery ceiling okay to cover
Rough-in6/6/20186/7/20186/7/2018APASS
DetailsBrian Scoles
rough in inspection for duct insulation . Tyson is your contact Phone #: ###-#### Inspection requested via web by Kim Adams- firewrap ok- ok to install ceiling tiles
Rough-in6/5/20186/7/20186/6/2018ACANC
DetailsChad Schwendiman
Rough in inspection for duct insulation - Antonio is your contact. Thank you! Phone #: ###-#### >> Inspection requested via web by Kim Adams Inspection cancelled from web by: Kim Adams
Rough-in5/31/20186/1/20186/1/2018APASS
DetailsChad Schwendiman
light test . Dave Dechambeau contact, Phone #: ###-#### - Light test pass for left kitchen hood
Rough-in5/30/20185/31/20185/31/2018PCANC
DetailsChad Schwendiman
light test . Dave Dechambeau contact, Phone #: ###-#### Inspection requested via web by Kim Adams
Rough-in5/29/20185/30/20185/30/2018APASS
DetailsChad Schwendiman
light test inspection. Dave Dechambeau is your contact Phone #: ###-#### Inspection requested via web by Kim Adams - Light test pass for right kitchen hood
Rough-in5/24/20185/25/20185/25/2018APASS
DetailsBen Livingston
Grease duct light test. Contact Dave DeChambeau ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty
tie in fittings grease duct deli 1
gease duct for kitchen left and right
Rough-in5/23/20185/24/20185/24/2018PPASS
DetailsChad Schwendiman
Grease duct light test Contact Dave DeChambeau ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty - Light test pass for wood burner
Rough-in5/23/20185/24/20185/24/2018APASS
DetailsChad Schwendiman
rough in inspection for above the ceiling Phone #: ###-#### Inspection requested via web by Kim Adams - okay to cover ceilings in mezzanine, and pharmacy
Rough-in5/21/20185/21/20185/21/2018PPASS
DetailsChad Schwendiman
Light test for meat smoker - Dave Dechambeau is your contact. Thank you! Phone #: ###-#### Inspection requested via web by Kim Adams
Rough-in5/17/20185/18/20185/18/2018APASS
DetailsBen Livingston
Grease duct light test on Deli Hood # 2 ; Meat Island Hood. Contact Dave DeChambeau ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty
meat island and deli. 2 grease duct ok
Rough-in5/14/20185/15/20185/15/2018APASS
DetailsChad Schwendiman
Rough in for Roof duct Contact Antonio ###-#### Phone #: ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty - Okay to insulate all the duct on the roof.
Rough-in5/11/20185/14/20185/14/2018AFAIL
DetailsChad Schwendiman
Rough in for Roof duct Contact Antonio ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty - Need to finish sealing the 4th system
Rough-in5/10/20185/11/20185/11/2018PPASS
DetailsChad Schwendiman
Grease duct light test at TML 120 E 40th.
Contact Steve Beason ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty - Light test pass
Rough-in5/11/20185/11/20185/11/2018PPASS
DetailsChad Schwendiman
Okay to insulate ducts on roof for AC-6, 14, & 15.
Rough-in5/10/20185/11/20185/11/2018APASS
DetailsChad Schwendiman
Grease duct light test at Albertsons job site.
Contact Dave DeChambeau ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty - Light test pass for bakery hood
Conference5/9/20185/10/20185/10/2018PDONE
DetailsChad Schwendiman
Light test grease duct. Contact is Steve here at TML officer on 120 E 40th St. Phone #: ###-#### Inspection requested via web by Kim Adams
Conference5/9/20185/10/20185/9/2018ACANC
DetailsChad Schwendiman
Grease duct light test at TML 102 E 40th. Contact Steve Beason ###-#### Phone #: ###-#### >> Inspection requested via web by Dan Flaherty Inspection cancelled from web by: Kim Adams
Conference4/30/20184/30/20184/30/2018PPASS
DetailsChad Schwendiman
At TML shop 120 E 40th street Grease duct light test. Contact Steve Beason ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty - Light test pass on 8ea. 10' drops with transitions
Rough-in4/23/20184/23/20184/23/2018PPASS
DetailsChad Schwendiman
Rough in Inspection ; Antonio is your contact. Thank you! Phone #: ###-#### Inspection requested via web by Kim Adams - duct work in pharmacy okay
Rough-in4/19/20184/19/20184/19/2018PPASS
DetailsChad Schwendiman
inspection for the front entry and the bakery. Antonio will be your contact. Thank you! Phone #: ###-#### Inspection requested via web by Kim Adams
Rough-in4/11/20184/11/20184/11/2018PPASS
DetailsChad Schwendiman
rough in inspection for the mezzanine - Antonio is your contact Phone #: ###-#### Inspection requested via web by Kim Adams - Duct seal okay on duct work in, and below mezannine
Rough-in4/2/20184/2/20184/2/2018PPART
DetailsChad Schwendiman
Rough In Inspection for Hard lids. Antonio will be your contact. Phone #: ###-#### Inspection requested via web by Kim Adams - Okay to cover hard lids in bathrooms in the north east corner of building.