Mec-Aging Inspection | 2/6/2019 | 2/6/2019 | 2/6/2019 | | DONE |
Chad Schwendiman
|
|
|
Permit expired. Contractor terminated contract with homeowner and another contractor went in and completed work.
|
DOC - Permit Expired | 2/6/2019 | 2/6/2019 | 2/6/2019 | A | PASS |
Chad Schwendiman
|
|
|
Permit is being expired do to no scheduled activity in the last 180 days. A new permit will need to pulled if further inspections are required.
|
Mec-Aging Inspection | 11/6/2018 | 11/6/2018 | 11/6/2018 | | FAIL |
Jack Reynolds
|
|
|
no inspection scheduled
|
Final | 2/20/2018 | 2/21/2018 | 2/21/2018 | A | FAIL |
Bill VanDegrift
|
|
|
10 am
waterheater corrections
1) permit required for installing a water heater 2) provide a water heater pan 3) T&P is trapped 4) remove flex connector fron T&P
furnace corrections
1) gas flex is undersized 2) seal between the furnace and coil 3) secure furnace flue 4) change condenser flex to weather tight. called contractor
|