Permit Information
Permit NumberMEC18-00631
StatusFinaled
Name DEBEST PLUMBING INC
Site Address 301 N 29TH ST
Project Name 
Customer Number17-65
ePlanReviewNo
Description
New: Hydronic, Condensate & Natural Gas Piping.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/8/20191/9/20191/9/2019PPASS
DetailsBen Livingston
if questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
Rough-in1/8/20191/8/20191/8/2019PPASS
DetailsBen Livingston
above ceiling condensate piping, if questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
all condensate complete
Pressure Test12/17/201812/18/201812/18/2018APASS
DetailsBen Livingston
if questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
60 lb gas water heaters 1st floor
Pressure Test12/11/201812/12/201812/12/2018APASS
DetailsBen Livingston
above ceiling inspection, call Glen when you are onsite ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
1st floor 60lb gas piping to 2 boilers, 2nd floor 60lb gas piping to water heater,
hydronic and condensate piping 1st and 2nd floor corridoors all units
Pressure Test11/30/201811/30/201811/30/2018PPASS
DetailsBen Livingston
if questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
final hydronics 1st and 2nd floor 100lb x4
gas piping both roofs 60lb x4
Pressure Test11/19/201811/20/201811/20/2018APASS
DetailsBen Livingston
if questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
100lb hydronic in mechanicalroom
Pressure Test11/16/201811/19/201811/19/2018AFAIL
DetailsBen Livingston
if questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
replacing butterfly valve, not holding pressure
Pressure Test11/13/201811/13/201811/13/2018PPASS
DetailsBen Livingston
if questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
100lb hydronic x4 east and west corridors
Pressure Test11/5/201811/5/201811/5/2018PPASS
DetailsBen Livingston
if questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
2nd floor 100lb hydronics from isolation valves x2.
2nd floor gas piping from valve to temp heat and tankless water heater 60lb
Pressure Test10/31/201810/31/201810/31/2018PPASS
DetailsBen Livingston
Gas test
from mechanical room to meter temp heat 60lb test daryl spivey
Rough-in10/30/201810/30/201810/30/2018PPASS
DetailsBen Livingston
if questions call Glen @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann
condensate piping in wall music room,
x2 6" hydronic lines in wall cafiteria to mechanical room 100lb test okay
Rough-in10/17/201810/17/201810/17/2018PPART
DetailsChad Schwendiman
if questions call Glen ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann - Condensate piping in the walls okay in rooms 205, 210, 219
Rough-in10/4/201810/5/201810/5/2018APASS
DetailsBen Livingston
If there are any questions please contact Glen B. at ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann
2 condensate lines in kitchen
Rough-in9/4/20189/4/20189/4/2018PPART
DetailsChad Schwendiman
condensate inspection, if questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann - Condensate piping in the walls okay for units in corridors D226, D207, and toilet room D215
Rough-in7/24/20187/25/20187/25/2018APASS
DetailsBen Livingston
condensate lines. If questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
condensate lines in walls area B okay
Pressure Test4/5/20184/5/20184/5/2018PPASS
DetailsBen Livingston
Pressure Test - underground lines to cooling tower. if questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
all underground piping to cooling tower 100lb x4
Pressure Test4/3/20184/4/20184/4/2018ACANC
DetailsBen Livingston
Mechanical pressure test - underground lines to cooling tower. if questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
Glen called to canc.
Pressure Test3/27/20183/28/20183/28/2018APASS
DetailsBen Livingston
hydronic line underground to cooling tower - Mechanical pressure test. if questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
supply and return 6"
1" Pipe to cooling town
2" none pottable 100lb test x4
Pressure Test3/26/20183/27/20183/27/2018ANR
DetailsBen Livingston
Pressure test for two chilled water pipes underground. If there are any questions please contact Glen B. at ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann