Final | 6/27/2018 | 6/28/2018 | 6/28/2018 | A | PASS |
Bill VanDegrift
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss
|
Final | 5/25/2018 | 5/29/2018 | 5/25/2018 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Krista Boss Inspection cancelled from web by: Krista Boss
|
Rough-in | 3/27/2018 | 3/28/2018 | 3/28/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss-rough okay
|
Rough-in | 3/26/2018 | 3/27/2018 | 3/27/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss- b vent needs insulation shield in attic- b vent firestop needs completely panned off so no insulation can fall into chase- b vent needs 1" clearance to combustibles at attic anf firecaulk completely
|
Rough-in | 3/23/2018 | 3/23/2018 | 3/23/2018 | P | FAIL |
Bill VanDegrift
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss 1) remove all insulation required for HVAC inspection 2) insulation shield required on b-vent from second floor floor to above insulation in attic 3) 20# gas test ok
|
Pressure Test | 3/23/2018 | 3/23/2018 | 3/23/2018 | P | PASS |
Bill VanDegrift
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss 20# gas test ok
|
Rough-in | 3/22/2018 | 3/22/2018 | 3/22/2018 | P | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss need approved manual j
|
Pressure Test | 3/22/2018 | 3/22/2018 | 3/22/2018 | P | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss test at zero
|