Final | 5/17/2018 | 5/18/2018 | 5/18/2018 | A | PASS |
Brian Scoles
|
|
|
MEC AND FIREPL CARAGE CODE 7373 Phone #: ###-#### Inspection requested via web by Oleg Chervak- fireplace final ok- final ok on HVAC
|
Final | 5/10/2018 | 5/11/2018 | 5/11/2018 | A | FAIL |
Brian Scoles
|
|
|
MEC AND FIREPL GARAGE CODE 7373 Phone #: ###-#### Inspection requested via web by Oleg Chervak- need 3 screws in single wall flue off water heater all joints- need uv protection on lineset outside- need rips and tears fixed on armaflex in furnace closet bare copper is visible
|
Rough-in | 3/8/2018 | 3/8/2018 | 3/8/2018 | P | PASS |
Brian Scoles
|
|
|
hvac r/i and f/p r/i - Oleg Phone #: ###-####- R/I ok- corrections made
|
Rough-in | 3/8/2018 | 3/8/2018 | 3/8/2018 | P | PASS |
Brian Scoles
|
|
|
hvac r/i and f/p r/i - Oleg Phone #: ###-####- fireplace R/I ok
|
Rough-in | 3/7/2018 | 3/7/2018 | 3/7/2018 | P | FAIL |
Brian Scoles
|
|
|
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak- furnace installed doesnt match manual J model #- need to support flex duct in crawl per manu install instructions no sags- insulation shield on fireplace flue needs to run full height to roof so no insulation can get on it- correction notice front window
|
Pressure Test | 3/7/2018 | 3/7/2018 | 3/7/2018 | P | PASS |
Brian Scoles
|
|
|
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass- 5lb flue pass
|
Pressure Test | 3/6/2018 | 3/7/2018 | 3/7/2018 | A | CANC |
Brian Scoles
|
|
|
LATE PM Phone #: ###-#### Inspection requested via web by Oleg Chervak
|
Rough-in | 3/6/2018 | 3/7/2018 | 3/7/2018 | A | CANC |
Brian Scoles
|
|
|
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak
|