Final | 5/7/2018 | 5/8/2018 | 5/8/2018 | A | PASS |
Brian Scoles
|
|
|
final - re-inspect Phone #: ###-#### Inspection requested via web by Brandon Sorensen- final ok
|
Final | 5/1/2018 | 5/2/2018 | 5/2/2018 | P | FAIL |
Brian Scoles
|
|
|
re-inspect for final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- flue on furnace can not be trapped like installed- needs 1/4" slope per foot
|
Final | 4/30/2018 | 5/1/2018 | 5/1/2018 | A | FAIL |
Brian Scoles
|
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- need drip leg on gas lines between shut off valve and appilance both W/H and furnace- need uv tape on lineset outside at A/C- flue pipe cannot be trapped need 1/4" per foot of slope and redone- need to insulate 6" fresh air in garage- left correction notice on furnace in garage
|
Rough-in | 3/15/2018 | 3/16/2018 | 3/16/2018 | A | PASS |
Brian Scoles
|
|
|
re-inspect for rough Phone #: ###-#### Inspection requested via web by Brandon Sorensen- R/I ok
|
Rough-in | 3/14/2018 | 3/15/2018 | 3/15/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Sorensen- fresh air/outside air to R/A plenum needs to be 6" per manual J- need line set installed on R/I- crawl duct needs more supports per manu installation- need nailplates on dryer vent ceiling and fire block both sides- corretion notice front window
|
Pressure Test | 3/14/2018 | 3/15/2018 | 3/15/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Sorensen- 20lb gas pass
|