Final | 8/1/2018 | 8/1/2018 | 8/1/2018 | P | PASS |
Brian Scoles
|
|
|
Bj. After 1 if possible. Makeup air is in the soffit Inspection requested via web by william kerwin- final ok- corrections made
|
Final | 7/30/2018 | 7/30/2018 | 7/30/2018 | P | FAIL |
Jack Reynolds
|
|
|
Bj 5730755 Inspection requested via web by william kerwin- cant use flex for range hood venting- also cant find make up air vent termination
|
Final | 7/26/2018 | 7/27/2018 | 7/27/2018 | A | FAIL |
Brian Scoles
|
|
|
Bj 5730755 Inspection requested via web by william kerwin- range ducting must be ran in hard duct not flex duct and sizing is smaller that hood exhaust- need to know where make up air comes from for range hood- need pvc 90 at drain in garage off primary
|
Rough-in | 3/29/2018 | 3/29/2018 | 3/29/2018 | P | PASS |
Brian Scoles
|
|
|
BJ ###-#### Inspection requested via web by william kerwin- R/I ok- Fireplace R/I ok
|
Rough-in | 3/22/2018 | 3/23/2018 | 3/23/2018 | A | FAIL |
Brian Scoles
|
|
|
J 573 0755 Inspection requested via web by william kerwin- fireplace needs plastic secured around firestop- need to insulate bare metal at R/A register in living room where front bedroom R/A ties in to ducting- need address clearly posted- correction notice front window
|
Pressure Test | 3/22/2018 | 3/23/2018 | 3/23/2018 | A | PASS |
Brian Scoles
|
|
|
J 573 0755 Inspection requested via web by william kerwin- 20lb gas pass
|