Permit Information
Permit NumberMEC18-01191
StatusFinaled
Name ALLEY HEATING & COOLING
Site Address 4685 N SUNDERLAND LN
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/6/20186/6/20186/6/2018PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Oleg Chervak- final ok
Final6/6/20186/6/20186/6/2018AFAIL
DetailsBrian Scoles
Final and fireplace please
Garage code is 7373 Phone #: ###-#### Inspection requested via web by Todd Campbell- fresh air in furnace closet still needs insulated
Final6/1/20186/4/20186/4/2018AFAIL
DetailsBrian Scoles
Mechanical and fireplace final.
Garage code is 7373. Phone #: ###-#### Inspection requested via web by Todd Campbell- need uv protection on line set outside at a/c- need to insulate 6" fresh air in furnace closet- need to install doors on furnace loset and install combustion air- fireplace needs tile/rock finished on face
Final6/1/20186/1/20186/1/2018AFAIL
DetailsBrian Scoles
Mechanical and fireplace final Phone #: ###-#### Inspection requested via web by Todd Campbell- no access house locked up
Final6/1/20186/1/20186/1/2018PCANC
DetailsBrian Scoles
FIREPL Phone #: ###-#### >> Inspection requested via web by Oleg Chervak Inspection cancelled from web by: Todd Campbell
Final6/1/20186/1/20186/1/2018ACANC
DetailsBrian Scoles
Phone #: ###-#### >> Inspection requested via web by Todd Campbell Inspection cancelled from web by: Todd Campbell
Pressure Test3/16/20183/16/20183/16/2018PPASS
DetailsBrian Scoles
Oleg Phone #: ###-####- R/I ok- Fireplace R/I ok
Rough-in3/15/20183/16/20183/16/2018AFAIL
DetailsBrian Scoles
FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak- fireplace metal firestop upside down inside of house- talk with Oleg about this-
Rough-in3/15/20183/15/20183/15/2018PFAIL
DetailsBrian Scoles
Oleg-fireplace Phone #: ###-####- fireplace fluing not installed per manufactures installation instruction- inner liner is missing screws and fire sealant- outer liner is missing sealant too-
Rough-in3/14/20183/15/20183/15/2018PPART
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Oleg Chervak- HVAC R/I ok
Pressure Test3/14/20183/15/20183/15/2018PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass
Rough-in3/14/20183/15/20183/15/2018AFAIL
DetailsBrian Scoles
FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak- need fireplace installation instructions onsite-