Final | 6/14/2018 | 6/15/2018 | 6/15/2018 | A | PASS |
Brian Scoles
|
|
|
Garage code #3162 Phone #: ###-#### Inspection requested via web by Debbie Marino- final ok
|
Final | 6/13/2018 | 6/14/2018 | 6/14/2018 | A | FAIL |
Brian Scoles
|
|
|
garage code #3162 Phone #: ###-#### Inspection requested via web by Debbie Marino- fresh air needs insulated in garage- primary drain needs supported- tape up rips on arma flex in garage- extend secondary drain down below wood
|
Conference | 6/13/2018 | 6/13/2018 | 6/13/2018 | P | PASS |
Brian Scoles
|
|
|
Duct Blast at 1:30pm Phone #: ###-#### Inspection requested via web by Debbie Marino- duct blast test pass
|
Conference | 4/9/2018 | 4/12/2018 | 4/12/2018 | P | CANC |
Brian Scoles
|
|
|
w duct blast 230 pm Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|
Rough-in | 3/27/2018 | 3/28/2018 | 3/28/2018 | P | PASS |
Brian Scoles
|
|
|
FP inspection also please Phone #: ###-#### Inspection requested via web by dannyel chaloupka- R/I ok
|
Rough-in | 3/28/2018 | 3/28/2018 | 3/28/2018 | P | PASS |
Brian Scoles
|
|
|
FP inspection also please Phone #: ###-#### Inspection requested via web by dannyel chaloupka- fireplace R/I ok
|
Pressure Test | 3/27/2018 | 3/28/2018 | 3/28/2018 | P | PASS |
Brian Scoles
|
|
|
FP inspection also please Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 20lb gas pass
|
Pressure Test | 3/26/2018 | 3/27/2018 | 3/27/2018 | P | CANC |
Brian Scoles
|
|
|
will do FP inspection later this week. Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|
Rough-in | 3/26/2018 | 3/27/2018 | 3/27/2018 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|