Permit Information
Permit NumberMEC18-01349
StatusFinaled
Name GUZMAN MECHANICAL HVAC LLC
Site Address 4711 W FRANKLIN RD
Project NameBasement conversion
Customer Number 
ePlanReviewNo
Description
Replace furnace, a/c, ducts and gas line
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/15/20191/17/20191/17/2019APASS
DetailsJack Reynolds
###-####
call 30 minutes ahead please try before 10:00am
- final ok
Final1/14/20191/15/20191/15/2019ANH
DetailsJack Reynolds
Please call ahead 20 minutes // Brie Phone #: ###-####
- no access to home left notice on front door
- reschedule with owner
Mec-Aging Inspection1/10/20191/10/20191/10/2019PDONE
DetailsJack Reynolds
Please go by when you have time and try to make contact with the homeowner, or leave a notice asking them to get a hold of us for a final inspection. Chad S.
- I was able to reach homeowner and perform a final inspection. Need to fix and check water heater flue for proper clearances- homeowner's infomation is Brea Witt ###-####
-
Mec-Aging Inspection12/27/201812/27/201812/27/2018 FAIL
DetailsJack Reynolds
need to schedule a final inspection for mech permit
Rough-in4/9/20184/10/20184/10/2018APASS
DetailsBen Livingston
Inspection requested via web by Baldomero Guzman
double check water heater vent clearances at final in basment coming through wall
Rough-in4/7/20184/9/20184/9/2018AFAIL
DetailsChad Schwendiman
Please call Baldo if nobody is at this address!. Thank you!
Phone #: ###-#### Inspection requested via web by Baldomero Guzman
1) Need approved manual J onsite.
2) Gas pressure fail
3) Need to complete ducting
4) Need to rough in condensate drains
5) Missing return air transfers in bedrooms
6) Missing nail plate on dryer duct
Do not cover mechanical systems
Rough-in4/3/20184/4/20184/4/2018PFAIL
DetailsChad Schwendiman
Please arrived after 1:00 pm. Please call Baldo if there is any problem or nobody is at home Phone #: ###-#### Inspection requested via web by Baldomero Guzman
Not ready