Permit Information
Permit NumberMEC18-01524
StatusFinaled
Name RM MECHANICAL
Site Address 6871 W OVERLAND RD
Project Name 
Customer NumberD17-066
ePlanReviewNo
Description
Alteration: Install one rtu w duct system, two class 1 hoods with ef''s, one mau, two ceiling cabinet ef''s.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/18/20185/21/20185/21/2018APASS
DetailsJack Reynolds
HVAC Final Contact: Trever Jensen ###-#### Phone #: ###-#### Inspection requested via web by RM Mechanical
- final ok - signed card
Final5/16/20185/17/20185/17/2018AFAIL
DetailsJack Reynolds
Contact Name: Trevor Jensen Phone #: ###-#### Inspection requested via web by RM Mechanical- east side hood needs to extend 6" past equipment edge - need stainless steel on ceiling in front of east hood 18" out
- west side hood needs to extend 6" past equipment edge- need balance report on hood and make up air
Final5/15/20185/15/20185/15/2018PPART
DetailsJack Reynolds
Contact Name: Trever Jensen Phone #: ###-#### Inspection requested via web by RM Mechanical- working on starting up equipment- still need an air balance- smoke detector- a little bit of drywall needs cutt back from grease duct in attic- gas line needs fixed by plumber
Rough-in4/9/20184/10/20184/10/2018APASS
DetailsBrian Scoles
###-####- cover inspection- R/I ok- ok to cover- will inspect factory built grease duct as installed
Rough-in4/9/20184/9/20184/9/2018PCANC
DetailsBrian Scoles
Requesting partial rough-in inspection for today.

Contact: Trever Jensen Phone #: ###-#### Inspection requested via web by Melissa Kaae- rescheduled for tomorrow AM
Rough-in4/6/20184/6/20184/6/2018PPART
DetailsBrian Scoles
Requesting partial rough-in for today.

Contact: Trever Jensen Phone #: ###-#### Inspection requested via web by Melissa Kaae- seal on remaining duct ok- ok to insulate- no cover yet
Rough-in4/5/20184/5/20184/5/2018PPART
DetailsBrian Scoles
Requesting partial rough-in, duct seal, inspection for this afternoon.

Contact: Trever Jensen Phone #: ###-#### Inspection requested via web by Melissa Kaae- SEAL ON DUCT DINING AREA ONLY OK TO INSULATE