Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberMEC18-01658
StatusFinaled
Name DEBEST PLUMBING INC
Site Address 305 E JEFFERSON ST
Project Name 
Customer Number17-81
ePlanReviewNo
Description
New: Hydronic, gas & condensate piping.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/17/20194/17/20194/17/2019PPASS
DetailsBen Livingston
if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
Final4/1/20194/2/20194/2/2019APART
DetailsBen Livingston
All floors ready for Mechanical Final. If questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
part final, 4 units in stairwells remain
Rough-in3/1/20193/4/20193/4/2019APASS
DetailsBen Livingston
ceiling cover 3rd ; 4th floors. if questions call Steve @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann
3rd and 4th floor Area1-9 okay 9-10 remain
Rough-in2/19/20192/21/20192/21/2019APASS
DetailsBen Livingston
1st ; 2nd floor mechanical ceiling cover. if questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
1st 2nd floor pass
Pressure Test2/4/20192/5/20192/5/2019PPASS
DetailsBen Livingston
before 4:30pm. Pressure Test on Penthouse Chilled ; Glycol Loops. If questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
100lb hydronics penthouse, final connections gas to boilers penthouse
Pressure Test1/23/20191/24/20191/24/2019PPASS
DetailsBen Livingston
west ; east LL-1 ; LL-3 CUH ; UH 100# pressure test. if questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
100lb hydronic
Pressure Test1/23/20191/23/20191/23/2019PPASS
DetailsBen Livingston
Hydronic Pressure Test - Penthouse heating pump. If questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
hydronic in penthouse 100lb x2
Pressure Test1/15/20191/16/20191/16/2019APASS
DetailsBen Livingston
pressure test on 2# gas main from meter to penthouse ; boilers, ; low pressure gas from meter to kitchen.
If questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
60lb on 2" main, 20lb on kitchen line
Pressure Test12/20/201812/20/201812/20/2018PPASS
DetailsBen Livingston
4th Hydronic mains ; branches to bypass 100#test. If questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
4th floor 100lb hydronics
Pressure Test12/17/201812/17/201812/17/2018PPASS
DetailsBen Livingston
hydronic pressure test - 3rd floor main loop to bypass. if questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
100 lb x2 3rd floor loop
Pressure Test11/1/201811/2/201811/2/2018APASS
DetailsBen Livingston
pressure test - 3rd floor hydronic mains and branches to VAV''s and shaft risers. If questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
100lb
Pressure Test10/2/201810/2/201810/2/2018PPASS
DetailsBen Livingston
LL-1 ; L-1 Hydronic 35# pressure test through fin tubes ; units. If questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
35lb test all fin tubes ll1 l1
Pressure Test9/20/20189/21/20189/21/2018APASS
DetailsBen Livingston
Pressure test gas main through 4th floor, if questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
60lb gas main to 4th floor
Pressure Test9/21/20189/21/20189/21/2018PPASS
DetailsBen Livingston
Pressure test ll1 fintubes 100lb test
Pressure Test9/7/20189/7/20189/7/2018PPASS
DetailsBen Livingston
1st floor. If questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
1st floor 11/4" gas line and kitchen 20lb
Pressure Test8/21/20188/22/20188/22/2018APART
DetailsBen Livingston
if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
20lb test on 11/4" gas pipe in wall for kitchen,
need a 30lb gauge
Pressure Test7/12/20187/13/20187/13/2018APASS
DetailsBen Livingston
If questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
2nd floor 100lb hydronic test x2
Pressure Test7/5/20187/9/20187/9/2018AFAIL
DetailsBen Livingston
L.L.-1, ; L-1, ; shaft piping, hydronic pressure test. If questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
walked parking garage and first floor hydronic 2 100lb tests, need approved plans on sight to pass inspection