Final | 5/9/2018 | 5/9/2018 | 5/9/2018 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Chris Field- final for open burner ok
|
Final | 5/3/2018 | 5/4/2018 | 5/3/2018 | A | CANC |
Jack Reynolds
|
|
|
Phone #: ###-#### >> Inspection requested via web by Chris Field Inspection cancelled from web by: Chris Field
|
Final | 4/13/2018 | 4/19/2018 | 4/19/2018 | A | NR |
Chad Schwendiman
|
|
|
SITE CONTACT: JOE WALSH ###-#### EXTEND GAS LINE FOR GRILL Phone #: ###-#### Inspection requested via web by Chris Field - Work isn't complete. I spoke with installer told him no pressure test needed, less than 10'ft of pipe. Need to bubble test joints. They are adding a open burner under an existing hood next to a fryer. I spoke with contractor and manager and let them know that and open flame closer than 16" to a fryer needs to have a shield in place that extends 8" above the top of the appliance thats the highest.
|