Final | 8/10/2018 | 8/10/2018 | 8/10/2018 | P | PASS |
Brian Scoles
|
|
|
Bj 2085730755 Inspection requested via web by william kerwin- final ok
|
Final | 8/1/2018 | 8/2/2018 | 8/2/2018 | A | PART |
Brian Scoles
|
|
|
Bj 5730755 Inspection requested via web by william kerwin- final ok pending airbalance report and other mech inspection from different contractors needs completed-
|
Rough-in | 7/19/2018 | 7/19/2018 | 7/19/2018 | P | PASS |
Brian Scoles
|
|
|
Ceiling grid cover. Bj 2085730755 Inspection requested via web by william kerwin- R/I ok- ok for ceiling tiles
|
Rough-in | 7/18/2018 | 7/18/2018 | 7/18/2018 | A | PART |
Brian Scoles
|
|
|
After 10 if possible. Ceiling grid cover inspection. Tha k You 2085730755 Inspection requested via web by william kerwin- need to add register to washer area by hood and omit 1 in that area- went over with installer- need access to duct detector above hard lid general contractor will take care of- need to finish sealing MAU duct - need time and a half tap on 16x14 supply duct in kitchen- recall in inspection when ready- no cover at this time
|
Rough-in | 4/24/2018 | 4/24/2018 | 4/24/2018 | P | PART |
Brian Scoles
|
|
|
Bj 5730755 Inspection requested via web by william kerwin- seal on duct ok- ok for hard lid cover only- need to install smoke detectors in R/A of units for before cover will be granted in rest of building
|
Rough-in | 4/20/2018 | 4/23/2018 | 4/23/2018 | A | FAIL |
Brian Scoles
|
|
|
J 208 573 0755 Inspection requested via web by william kerwin- damper handle missing on supple branch north east RTU middle supply line - drives on ductwork need to be sealed and bent over- ductwork hangers need to be extended below duct with three screws- need nail plates on lineset for mini split in front of building on east side- felt correction notice on front window frame
|