Final | 5/29/2018 | 5/29/2018 | 5/29/2018 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee- final ok- card signed
|
Final | 5/23/2018 | 5/25/2018 | 5/25/2018 | P | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee - need 1" clearances to b vent going through roof and need insulation sheild to maintain 1" clearances to insulation- Need to seal 4" PVC goose neck- need to support line set on roof
|
Rough-in | 5/1/2018 | 5/1/2018 | 5/1/2018 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee- breakroom ok for cover
|
Rough-in | 4/30/2018 | 5/1/2018 | 5/1/2018 | A | PART |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee- Supply ducting and exhaust fans ok- need to finish return ducting into space for ok to cover ceiling
|