Final | 8/30/2018 | 8/30/2018 | 8/30/2018 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Steve Torgerson- final ok
|
Rough-in | 8/27/2018 | 8/27/2018 | 8/27/2018 | A | PASS |
Jack Reynolds
|
|
|
inspect wiring to cover Phone #: ###-#### Inspection requested via web by Steve Torgerson R/I ok- comm and fire wire is plenum rated and ok- ok for cover
|
Rough-in | 8/20/2018 | 8/20/2018 | 8/20/2018 | A | FAIL |
Jack Reynolds
|
|
|
checking on plenum rated wire in ceiling by data and fire - Blue Comm wire needs to be plenum rated - Red fire alarm wire needs to be plenum rated
|
Rough-in | 8/2/2018 | 8/3/2018 | 8/3/2018 | A | PART |
Jack Reynolds
|
|
|
seal inspection--see Richard on sie Inspection requested via web by Steve Torgerson- duct seal ok- have questions on return plenum and type of wire ran within the plenum
|
Rough-in | 7/5/2018 | 7/5/2018 | 7/5/2018 | P | FAIL |
Jack Reynolds
|
|
|
Seal and cover inspection on new ductwork. Phone #: ###-#### Inspection requested via web by Steve Torgerson- needs city of boise approved plans onsite
|