Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberMEC18-02236
StatusExpired
Name 1A HEATING AND COOLING
Site Address 2207 W OVERLAND RD
Project NameBabylon Market LLC
Customer Number 
ePlanReviewNo
Description
install type 1 hood 20', run gas line, & spiral duct
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Mec-Aging Inspection3/10/20203/10/20203/10/2020 PASS
DetailsJack Reynolds
Doc Permit Expired ok
DOC - Permit Expired3/10/20203/10/20203/10/2020APASS
DetailsJack Reynolds
Doc Permit Expired ok permit not active
Mec-Aging Inspection12/10/201912/10/201912/10/2019 FAIL
DetailsJack Reynolds
Permit has not been active since talking with the contractor. Type1 hood still has corrections that need made. Schedule inspection if corrections have been made. Permit will expired at next mechanical aging inspection if not active.
Mec-Aging Inspection9/10/20199/10/20199/10/2019 DONE
DetailsJack Reynolds
WIP
Mec-Aging Inspection6/11/20196/11/20196/11/2019 DONE
DetailsJack Reynolds
Progress at location has stopped and several items still need taken care of. Permit has not been active since 12/12/2018
Mec-Aging Inspection3/12/20193/12/20193/12/2019 DONE
DetailsJack Reynolds
Permit will expire in 180 days if not active
Pressure Test12/11/201812/12/201812/12/2018APASS
DetailsJack Reynolds
Call prior to going Phone #: 2088718789 >> Inspection requested via mobile web by Albert
- 60lb gas pressure test ok
Rough-in8/17/20188/17/20188/17/2018APART
DetailsJack Reynolds
Call for access Phone #: 2088718789 >> Inspection requested via mobile web by Albert
- first layer of fire wrap ok
Rough-in8/15/20188/16/20188/16/2018APART
DetailsJack Reynolds
Call for access Phone #: 2088718789 >> Inspection requested via mobile web by Albert
- x2 grease duct light test ok- ok for duct fire wrap
- will need to see clearance reduction put in place above hood- will also need to see exhaust fan on roof 10' away or 3' above make up air intake
Rough-in8/13/20188/14/20188/14/2018AFAIL
DetailsJack Reynolds
Call for access Phone #: 2088718789 >> Inspection requested via mobile web by Albert
- light test fail- also need clearances on exhuast fans to make-up unit on roof- a beam on the back side of the hood is within 18 " of hood top