Mec-Aging Inspection | 3/10/2020 | 3/10/2020 | 3/10/2020 | | PASS |
Jack Reynolds
|
|
|
Doc Permit Expired ok
|
DOC - Permit Expired | 3/10/2020 | 3/10/2020 | 3/10/2020 | A | PASS |
Jack Reynolds
|
|
|
Doc Permit Expired ok permit not active
|
Mec-Aging Inspection | 12/10/2019 | 12/10/2019 | 12/10/2019 | | FAIL |
Jack Reynolds
|
|
|
Permit has not been active since talking with the contractor. Type1 hood still has corrections that need made. Schedule inspection if corrections have been made. Permit will expired at next mechanical aging inspection if not active.
|
Mec-Aging Inspection | 9/10/2019 | 9/10/2019 | 9/10/2019 | | DONE |
Jack Reynolds
|
|
|
WIP
|
Mec-Aging Inspection | 6/11/2019 | 6/11/2019 | 6/11/2019 | | DONE |
Jack Reynolds
|
|
|
Progress at location has stopped and several items still need taken care of. Permit has not been active since 12/12/2018
|
Mec-Aging Inspection | 3/12/2019 | 3/12/2019 | 3/12/2019 | | DONE |
Jack Reynolds
|
|
|
Permit will expire in 180 days if not active
|
Pressure Test | 12/11/2018 | 12/12/2018 | 12/12/2018 | A | PASS |
Jack Reynolds
|
|
|
Call prior to going Phone #: 2088718789 >> Inspection requested via mobile web by Albert - 60lb gas pressure test ok
|
Rough-in | 8/17/2018 | 8/17/2018 | 8/17/2018 | A | PART |
Jack Reynolds
|
|
|
Call for access Phone #: 2088718789 >> Inspection requested via mobile web by Albert - first layer of fire wrap ok
|
Rough-in | 8/15/2018 | 8/16/2018 | 8/16/2018 | A | PART |
Jack Reynolds
|
|
|
Call for access Phone #: 2088718789 >> Inspection requested via mobile web by Albert - x2 grease duct light test ok- ok for duct fire wrap - will need to see clearance reduction put in place above hood- will also need to see exhaust fan on roof 10' away or 3' above make up air intake
|
Rough-in | 8/13/2018 | 8/14/2018 | 8/14/2018 | A | FAIL |
Jack Reynolds
|
|
|
Call for access Phone #: 2088718789 >> Inspection requested via mobile web by Albert - light test fail- also need clearances on exhuast fans to make-up unit on roof- a beam on the back side of the hood is within 18 " of hood top
|