Final | 8/24/2018 | 8/27/2018 | 8/27/2018 | P | PASS |
Brian Scoles
|
|
|
gate code:9898 access code to the home; 6365 Phone #: ###-#### Inspection requested via web by Gary Reeves- final ok
|
Final | 8/23/2018 | 8/24/2018 | 8/24/2018 | A | FAIL |
Brian Scoles
|
|
|
the gate code to get into the neighborhood is #9898 and the access code to get inside the home is 6365 Phone #: ###-#### Inspection requested via web by Gary Reeves- need air balance report and duct blast test completed
|
Rough-in | 6/8/2018 | 6/11/2018 | 6/11/2018 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves
|
Rough-in | 6/6/2018 | 6/6/2018 | 6/6/2018 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
|
Rough-in | 6/4/2018 | 6/4/2018 | 6/4/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- correction not made- supply register in master bedroom still hanging out in attic
|
Pressure Test | 6/4/2018 | 6/4/2018 | 6/4/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass
|
Rough-in | 5/30/2018 | 5/31/2018 | 5/31/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- coil size does not match manual J- exhaust fans need sealed where galv 90 tie onto fan- dryer vent at ceiling needs notched out farther duct is outside wall/ replace adjustable 90 thats smashed from nail plate- need supply and return install in ceiling master bedroom- relieve hanger pressure on gas pipe in wall behind furnace or reroute so no stress on pipe- gauge wont zero out- left notice front window
|
Pressure Test | 5/30/2018 | 5/31/2018 | 5/31/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- gauge doesnt zero out
|