Final | 12/12/2018 | 12/13/2018 | 12/13/2018 | P | PASS |
Ben Livingston
|
|
|
call for access Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN per direction from engineering team to address condensate problem, heat pumps are for cooling only and will heat from internal heat strip.
|
Final | 11/13/2018 | 11/13/2018 | 11/13/2018 | P | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSENarmaflex needs uv protection, need 2nd condensate drain ran, not all units have balance report
|
Rough-in | 5/22/2018 | 5/22/2018 | 5/22/2018 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|