Final | 1/24/2019 | 1/25/2019 | 1/25/2019 | A | PASS |
Troy James
|
|
|
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth
|
Final | 12/5/2018 | 12/6/2018 | 12/6/2018 | A | PART |
Troy James
|
|
|
Okay temp Ocupancy 3rd and 2nd floor
|
Final | 12/5/2018 | 12/5/2018 | 12/5/2018 | P | CANC |
Troy James
|
|
|
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth Rescheduled for morning
|
Conference | 7/30/2018 | 7/30/2018 | 7/30/2018 | P | PASS |
Troy James
|
|
|
Mtg at 1:00pm Met with contractors, engineer and architects to discuss resolutions for plumbing piping in ducted and return plenum shaft.
|
Conference | 7/25/2018 | 7/26/2018 | 7/26/2018 | A | PASS |
Troy James
|
|
|
Meet with plumbing and mechanical contractor Left correction notice to building contractor with code section stating the plumbing system cannot be in the hvac shaft.
|
Rough-in | 7/25/2018 | 7/25/2018 | 7/25/2018 | P | PASS |
Troy James
|
|
|
Inspected ducts for cover. Went over fire/smoke dampers requirements at shafts
|
Rough-in | 6/8/2018 | 6/8/2018 | 6/8/2018 | A | PASS |
Troy James
|
|
|
Okay to cover blue duct per ICC ES report.
|
Rough-in | 5/24/2018 | 5/25/2018 | 5/25/2018 | A | FAIL |
Troy James
|
|
|
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth Underground duct is required to slope 1/8" per foot to access port. IMC 2012 section 603.8.1
|