Permit Information
Permit NumberMEC18-02334
StatusFinaled
Name HOBSON FABRICATING CORP
Site Address 8000 S FEDERAL WAY
Project NameC30616 B37 Office Building
Customer Numberh9297
ePlanReviewNo
Description
Alteration: MICRON B37 OFFICE BUILDING, HVAC UNDERGOUND
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/24/20191/25/20191/25/2019APASS
DetailsTroy James
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth
Final12/5/201812/6/201812/6/2018APART
DetailsTroy James
Okay temp Ocupancy 3rd and 2nd floor
Final12/5/201812/5/201812/5/2018PCANC
DetailsTroy James
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth
Rescheduled for morning
Conference7/30/20187/30/20187/30/2018PPASS
DetailsTroy James
Mtg at 1:00pm
Met with contractors, engineer and architects to discuss resolutions for plumbing piping in ducted and return plenum shaft.
Conference7/25/20187/26/20187/26/2018APASS
DetailsTroy James
Meet with plumbing and mechanical contractor
Left correction notice to building contractor with code section stating the plumbing system cannot be in the hvac shaft.
Rough-in7/25/20187/25/20187/25/2018PPASS
DetailsTroy James
Inspected ducts for cover. Went over fire/smoke dampers requirements at shafts
Rough-in6/8/20186/8/20186/8/2018APASS
DetailsTroy James
Okay to cover blue duct per ICC ES report.
Rough-in5/24/20185/25/20185/25/2018AFAIL
DetailsTroy James
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth
Underground duct is required to slope 1/8" per foot to access port. IMC 2012 section 603.8.1