Final | 8/8/2018 | 8/8/2018 | 8/8/2018 | P | PASS |
Brian Scoles
|
|
|
Please contact Jasper with any questions. Thanks! Phone #: ###-#### Inspection requested via web by Ted Dumont
|
Final | 8/2/2018 | 8/3/2018 | 8/3/2018 | A | FAIL |
Chad Schwendiman
|
|
|
Please contact Jasper to meet you on site. Please give us 20 minutes notice. Phone #: ###-#### Inspection requested via web by Ted Dumont - Breaker for A/C is oversized, need to seal where lineset penetrates the exterior of te house, Need to extend the pad under the condensing unit out to the edge of the condensing unit
|
Final | 8/2/2018 | 8/2/2018 | 8/2/2018 | P | CANC |
Brian Scoles
|
|
|
Please contact Jasper Hoff Phone #: ###-#### >> Inspection requested via web by Ted Dumont Inspection cancelled from web by: Ted Dumont
|