Final | 11/16/2018 | 11/19/2018 | 11/19/2018 | A | PASS |
Jack Reynolds
|
|
|
please call dan before arrival: ###-#### thank you Phone #: ###-#### Inspection requested via web by Aaron Alandt - final ok
|
Rough-in | 6/26/2018 | 6/27/2018 | 6/27/2018 | A | PART |
Jack Reynolds
|
|
|
early pm if possible please thank you Phone #: ###-#### Inspection requested via web by Aaron Alandt- partial R/I waiting to see a permit pulled for the firplace by other before full R/I given for cover
|
Pressure Test | 6/26/2018 | 6/27/2018 | 6/27/2018 | A | PASS |
Jack Reynolds
|
|
|
early pm if possible please thank you Phone #: ###-#### Inspection requested via web by Aaron Alandt- 5lb furnace flue pressure test ok
|
Pressure Test | 6/26/2018 | 6/26/2018 | 6/26/2018 | P | PART |
Jack Reynolds
|
|
|
EARLY P.M. Inspection requested via web by Aaron Alandt- 20lb gas pressure test ok stickered meter bar- water heater 5lb flue test ok- furnace 5lb flue test failed gauge was at 5lb when i arrived but had dropped below 5lb while i checked the rest of the job
|
Rough-in | 6/26/2018 | 6/26/2018 | 6/26/2018 | P | PART |
Jack Reynolds
|
|
|
EARLY P.M. Inspection requested via web by Aaron Alandt- transfer airs ok- ductboard return sealed ok- the furnace flue 5lb test failed gauge was below 5lb- water heater 5lb flue test ok- 20lb gas pressure test ok stickered meter bar- need to see furnace flue pressure test and need to see that fireplace installers pull a MEC permit before i approve this permit for full R/I cover
|
Rough-in | 6/18/2018 | 6/20/2018 | 6/20/2018 | P | PART |
Jack Reynolds
|
|
|
please call mike at ###-#### with any questions. thank you Phone #: ###-#### Inspection requested via web by Aaron Alandt -east side first floor supply duct ok- line set on first floor ok- exhaust fans ducting ok- need to cap off duct board return upstairs and seal-need to see transfer airs from bedroom upstairs- need to have combustion air for laundry closet upstairs- need to witness 5lb flue pressure test x2 before cover downstairs- need to also find out whats happening with existing fireplace flue
|
Rough-in | 6/15/2018 | 6/19/2018 | 6/18/2018 | P | CANC |
Jack Reynolds
|
|
|
late pm inspection if possible please. thank you! Phone #: ###-#### >> Inspection requested via web by Aaron Alandt Inspection cancelled from web by: Aaron Alandt
|