Mec-Aging Inspection | 9/27/2019 | 9/27/2019 | 9/27/2019 | | PASS |
Jack Reynolds
|
|
|
Doc Permit Expired ok permit not active
|
DOC - Permit Expired | 9/27/2019 | 9/27/2019 | 9/27/2019 | A | PASS |
Jack Reynolds
|
|
|
No calls or attempts to schedule inspection. Permit has not been active since 12-11-18 when it failed a R/I inspection. Doc Permit Expired ok
|
Mec-Aging Inspection | 6/28/2019 | 6/28/2019 | 6/28/2019 | | FAIL |
Jack Reynolds
|
|
|
This permit still has no activities after failing a R/I inspection. Schedule an inspection if corrections have been made. Permit will expire at the next mechanical aging inspection if not active.
|
Mec-Aging Inspection | 3/29/2019 | 3/29/2019 | 3/29/2019 | | DONE |
Jack Reynolds
|
|
|
Called and talked with Trade Source about their mechanical aging permit. Ths permit has never been passed on a R/I inspection and many items that need to be fixed before a R/I passes. When ready for a final we will need to see a balance report and duct blast performed as well
|
Rough-in | 12/10/2018 | 12/11/2018 | 12/11/2018 | A | FAIL |
Jack Reynolds
|
|
|
Joe Phone #: ###-#### - Man J. doesnt match whats installed - Man J. needs basement layout added - gas line in attic needs supported - house has a gas leak inside somewhere (called the gas company to inform them of gas leak) and was told that they would want to see a gas pressure test performed by the city - lineset in attic needs supported - condensate line outside needs supported - drain pan below furnace in the attic needs a wet switch -supply branches need balance dampers - all bedrooms upstairs and downstairs need a transfer or ducted return - home owner needs to add bathroom exhaust fans to his own permit - all work needs to be performed by permit holder
|
Rough-in | 12/7/2018 | 12/10/2018 | 12/10/2018 | A | FAIL |
Jack Reynolds
|
|
|
call 15 mins- ###-#### Joe- Inspection requested via web by Richard Cusimano - need approved man J with stamp onsite - need access to attic to check duct work and furnace - bathroom downstairs needs an exhaust fan roughed in - need to see a gas pressure test - condensate line coming from the attic needs to be ran down the exterior wall to the ground
|
Conference | 10/22/2018 | 10/22/2018 | 10/22/2018 | P | FAIL |
Jack Reynolds
|
|
|
Inspection on HVAC needs to be called in for a R/I
|