Permit Information
Permit NumberMEC18-02743
StatusExpired
Name THE TRADE SOURCE
Site Address 1430 S COLORADO AVE
Project NameLitster Kitchen
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Retro-Fit Furnace, AC and Evaporator Coil
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Mec-Aging Inspection9/27/20199/27/20199/27/2019 PASS
DetailsJack Reynolds
Doc Permit Expired ok permit not active
DOC - Permit Expired9/27/20199/27/20199/27/2019APASS
DetailsJack Reynolds
No calls or attempts to schedule inspection. Permit has not been active since 12-11-18 when it failed a R/I inspection. Doc Permit Expired ok
Mec-Aging Inspection6/28/20196/28/20196/28/2019 FAIL
DetailsJack Reynolds
This permit still has no activities after failing a R/I inspection. Schedule an inspection if corrections have been made. Permit will expire at the next mechanical aging inspection if not active.
Mec-Aging Inspection3/29/20193/29/20193/29/2019 DONE
DetailsJack Reynolds
Called and talked with Trade Source about their mechanical aging permit. Ths permit has never been passed on a R/I inspection and many items that need to be fixed before a R/I passes. When ready for a final we will need to see a balance report and duct blast performed as well
Rough-in12/10/201812/11/201812/11/2018AFAIL
DetailsJack Reynolds
Joe Phone #: ###-####
- Man J. doesnt match whats installed
- Man J. needs basement layout added
- gas line in attic needs supported
- house has a gas leak inside somewhere
(called the gas company to inform them of gas leak) and was told that they would want to see a gas pressure test performed by the city
- lineset in attic needs supported
- condensate line outside needs supported
- drain pan below furnace in the attic needs a wet switch
-supply branches need balance dampers
- all bedrooms upstairs and downstairs need a transfer or ducted return
- home owner needs to add bathroom exhaust fans to his own permit
- all work needs to be performed by permit holder
Rough-in12/7/201812/10/201812/10/2018AFAIL
DetailsJack Reynolds
call 15 mins- ###-#### Joe- Inspection requested via web by Richard Cusimano
- need approved man J with stamp onsite
- need access to attic to check duct work and furnace
- bathroom downstairs needs an exhaust fan roughed in
- need to see a gas pressure test
- condensate line coming from the attic needs to be ran down the exterior wall to the ground
Conference10/22/201810/22/201810/22/2018PFAIL
DetailsJack Reynolds
Inspection on HVAC needs to be called in for a R/I