Pressure Test | 10/16/2018 | 10/16/2018 | 10/16/2018 | P | PASS |
Ben Livingston
|
|
|
Re-inspection Phone #: ###-#### Inspection requested via web by Julie McMillan 20lb x2
|
Final | 10/16/2018 | 10/16/2018 | 10/16/2018 | P | PASS |
Ben Livingston
|
|
|
Re-inspection Phone #: ###-#### Inspection requested via web by Julie McMillan
|
Pressure Test | 10/15/2018 | 10/16/2018 | 10/16/2018 | A | FAIL |
Chad Schwendiman
|
|
|
Re-inspection Phone #: ###-#### Inspection requested via web by Julie McMillan - Piping not under pressure
|
Rough-in | 10/11/2018 | 10/11/2018 | 10/11/2018 | P | PASS |
Ben Livingston
|
|
|
Re-inspection Phone #: ###-#### Inspection requested via web by Julie McMillan
|
Final | 10/8/2018 | 10/9/2018 | 10/9/2018 | A | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Julie McMillan need to run 2nd condensate drain, or wet switch, need to use pvc couplers on flue rubber ones not approved
|
Rough-in | 7/31/2018 | 8/1/2018 | 8/1/2018 | A | PASS |
Ben Livingston
|
|
|
Re-inspection - ASAP Please Phone #: ###-#### Inspection requested via web by Julie McMillan 5lb flue x2 roughin
|
Pressure Test | 8/1/2018 | 8/1/2018 | 8/1/2018 | A | PART |
Ben Livingston
|
|
|
Re-inspection - ASAP Please Phone #: ###-#### Inspection requested via web by Julie McMillan
20lb pass left tag 2nd needs 30 lb gauge
|
Rough-in | 7/30/2018 | 7/31/2018 | 7/31/2018 | A | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Julie McMillan need approved manual J on site for inspection, no fresh air to return plenum both gas pressure tests below 20 lbs
|