Final | 12/18/2018 | 12/19/2018 | 12/19/2018 | A | PASS |
Jack Reynolds
|
|
|
Mike Phone #: ###-#### final ok
|
Rough-in | 11/1/2018 | 11/1/2018 | 11/1/2018 | P | PASS |
Jack Reynolds
|
|
|
Mike-vents for dryer and duct work for furnace Phone #: ###-####- R/I ok
|
Rough-in | 10/31/2018 | 10/31/2018 | 10/31/2018 | P | NH |
Jack Reynolds
|
|
|
Mike Phone #: ###-####- no access to home and i still need to see duct work and dryer vent added to permit
|
Rough-in | 10/22/2018 | 10/22/2018 | 10/22/2018 | P | FAIL |
Jack Reynolds
|
|
|
Mike Phone #: ###-####- Duct work and furnace ok- line set in wall has rips in the insulation that need repaired- lineset needs supported in ceiling space- condensate needs supported in ceiling space - need to see dryer vent finished looks to still be inside the wall - need to also add duct work and dryer vent to permit
|