Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMEC18-03649
StatusFinaled
Name BUSS MECHANICAL SERVICES INC
Site Address 2121 N COLE RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: GAS PIPING
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/19/20196/19/20196/19/2019PPASS
DetailsBrian Scoles
JOHN IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER- final ok
Final5/15/20195/15/20195/15/2019APART
DetailsBrian Scoles
20lb gas pass from roof to 4 water heaters- drip legs on roof cannot be in contact with roof need to support- 2 of the water heaters have sediment traps before shutoff valves needs to be after- went over with contractor onsite
Final5/14/20195/15/20195/15/2019APART
DetailsBrian Scoles
JOHN IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER- 60lb gas test roof from open tee to RTUs pass- need to see 20lb test on welded pipe to water heaters still
Final3/21/20193/21/20193/21/2019APART
DetailsBrian Scoles
TCO for caffeteria and kitchen only ok- still need to test rest of gas line to locker rooms on roof
Pressure Test1/28/20191/29/20191/29/2019APART
DetailsBrian Scoles
JOHN IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER- 60lb gas pass roof for RTUs- tagged meter gas piping- will need to test locker room to water heaters when roof is completed and gas is ran