Permit NumberMEC18-03664
StatusFinaled
Name PAIGE MECHANICAL GROUP INC
Site Address 6452 S FEDERAL WAY
Project Name 
Customer Number18.6998.23
ePlanReviewNo
Description
Alteration: HVAc equipment, trim, duct, gas piping.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/19/201810/22/201810/22/2018APASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Nicholas Paige- balance report for pizza oven ok- final ok- card signed
Rough-in10/3/201810/4/201810/4/2018APART
DetailsJack Reynolds
Grease duct light inspection Phone #: ###-#### Inspection requested via web by Nicholas Paige- grease duct light test ok- partial ceiling cover on west side
Rough-in10/1/201810/2/201810/2/2018APASS
DetailsTroy James
Phone #: ###-#### Inspection requested via web by Nicholas Paige
ok second layer of grease duct wrap
Rough-in9/27/20189/28/20189/28/2018APART
DetailsJack Reynolds
grease duct Phone #: ###-#### Inspection requested via web by Nicholas Paige- 1st layer of grease duct wrap ok
Rough-in9/25/20189/26/20189/26/2018APART
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Nicholas Paige- light test on grease duct for pizza oven ok- still need to see two seams at the top and bottom of grease duct- ok for 1st layer of wrap dont not cover top and bottom seams
Rough-in9/24/20189/25/20189/25/2018APART
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Nicholas Paige- duct work insulation ok- still need to see light test on grease duct- not completely sure what needed to be seen on this R/I tried calling foreman
Pressure Test9/7/20189/7/20189/7/2018PPASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Nicholas Paige-60lb gas pressure test ok- tagged meter- needed another test because gas was being switched to high pressure
Pressure Test8/8/20188/9/20188/9/2018APASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Nicholas Paige- 20lb gas pressure test ok
Rough-in7/26/20187/27/20187/27/2018APART
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Nicholas Paige- all ducting in uncondtioned space needs to be lined or insulated on the outside- duct seal ok