Mec-Aging Inspection | 7/12/2019 | 7/12/2019 | 7/12/2019 | | PASS |
Jack Reynolds
|
|
|
doc permit expired ok
|
DOC - Permit Expired | 7/12/2019 | 7/12/2019 | 7/12/2019 | A | PASS |
Jack Reynolds
|
|
|
Doc permit expired ok
|
Mec-Aging Inspection | 4/12/2019 | 4/12/2019 | 4/12/2019 | | FAIL |
Jack Reynolds
|
|
|
- Electrical permit has not been pulled for electrical work being done on mini split - Schedule inspection once all corrections have been made -permit will expire in 180 days if not active
|
Final | 9/7/2018 | 9/14/2018 | 9/14/2018 | P | FAIL |
Jack Reynolds
|
|
|
Please call Rebecca 30 min prior. Would like early afternoon needs to leave by 430 Pm Phone #: ###-#### Inspection requested via web by Andrea Grigsby- need an eletrical permit pulled for system- not sure what breaker is the disconnect in the panel and the min breaker size is to be a 35 amp all breakers inside panel are 30amp and below- need to seal condesate penetration on the north side of house and add another support- condensates on the south side need to have flex tube inside the cover or pvc ran all the way into the cover cant have flex tube exposed to the outdoors- lineset covers need sealed at the ends
|