DOC - Permit Expired | | | 10/9/2019 | | DONE |
|
|
|
|
Final | 8/23/2019 | 8/26/2019 | 8/26/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Denise Colin- 1- still need to support lineset in crawl- 2- still needs 2nd switch installed
|
Mec-Aging Inspection | 5/31/2019 | 5/31/2019 | 5/31/2019 | | FAIL |
Jack Reynolds
|
|
|
If corrections have been made schedule inspection with homeowner. Permit will expire after 180 days and will have to be re issued if not active
|
Final | 3/1/2019 | 3/4/2019 | 3/4/2019 | A | FAIL |
Jack Reynolds
|
|
|
Inspection requested via web by Marisa Hone - need to see a working co detector installed home owner was wanting to have co detector installed where she can access it - lineset penetration needs sealed - lineset insulation is missing in crawl in two locations - lineset needs supported in crawl - secondary drain on indoor coil needs a wet switch installed
|