Final | 12/28/2018 | 1/2/2019 | 1/2/2019 | A | PASS |
Jack Reynolds
|
|
|
call thomas for questions ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt - final ok - man j ok
|
Conference | 12/19/2018 | 12/20/2018 | 12/20/2018 | A | DONE |
Jack Reynolds
|
|
|
LATE A.M. CONFERENCE PLEASE CALL DUSTIN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt -met with Dustin from western hvac - dryer vent is free of screws and roof cap is ok - condensate for furnace is ok and support of condensate is ok - gas line sediment trap ok and supports ok - water heater b vent 1" clearances ok - exhaust fans ducting ok - still need to see a Man J performed and onsite with balance and duct blast report -supplys needs balance dampers - attic access needs pathway finished and platform needs extended
|
Conference | 12/18/2018 | 12/19/2018 | 12/19/2018 | A | CANC |
Jack Reynolds
|
|
|
late a.m. with Dustin ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt - cancelled this will be rescheduled for tomorrow morning
|
Final | 12/18/2018 | 12/18/2018 | 12/18/2018 | P | FAIL |
Jack Reynolds
|
|
|
THOMAS IS CONTACT PERSON ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt - need Man J performed and stamped onsite -need balance report and duct blast onsite - need a level platform in front of furnace in attic at least 30" - condensate needs support on outside of house - secondary drain and pan needs a wet switch - gas line in attic needs support and a sediment trap - dryer vent did not have nail plates in photos that were provided - dryer vent cap needs to be an approved cap with no screens and a backdrft damper - need to see exhaust fans duct work - supply duct work needs balance dampers - water heater flue needs 1" clearances - this inspection should have been a R/I
|