Permit Information
Permit NumberMEC18-04154
StatusFinaled
Name WESTERN HEATING & A/C
Site Address 368 W HULBE DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: REMODEL - REPLACE FURNACE, RUN 2 BATH FANS, 1 DRYER VENT
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/28/20181/2/20191/2/2019APASS
DetailsJack Reynolds
call thomas for questions ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- final ok
- man j ok
Conference12/19/201812/20/201812/20/2018ADONE
DetailsJack Reynolds
LATE A.M. CONFERENCE PLEASE CALL DUSTIN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
-met with Dustin from western hvac
- dryer vent is free of screws and roof cap is ok
- condensate for furnace is ok and support of condensate is ok
- gas line sediment trap ok and supports ok
- water heater b vent 1" clearances ok
- exhaust fans ducting ok
- still need to see a Man J performed and onsite with balance and duct blast report
-supplys needs balance dampers
- attic access needs pathway finished and platform needs extended
Conference12/18/201812/19/201812/19/2018ACANC
DetailsJack Reynolds
late a.m. with Dustin ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- cancelled this will be rescheduled for tomorrow morning
Final12/18/201812/18/201812/18/2018PFAIL
DetailsJack Reynolds
THOMAS IS CONTACT PERSON ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- need Man J performed and stamped onsite
-need balance report and duct blast onsite
- need a level platform in front of furnace in attic at least 30"
- condensate needs support on outside of house
- secondary drain and pan needs a wet switch
- gas line in attic needs support and a sediment trap
- dryer vent did not have nail plates in photos that were provided
- dryer vent cap needs to be an approved cap with no screens and a backdrft damper
- need to see exhaust fans duct work
- supply duct work needs balance dampers
- water heater flue needs 1" clearances
- this inspection should have been a R/I