Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberMEC18-04245
StatusFinaled
Name BAYMAR MECHANICAL
Site Address 2115 W SUNRISE RIM RD
Project Name 
Customer Number 
ePlanReviewNo
Description
retro fit furnace & A/C
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/5/20189/6/20189/6/2018APASS
DetailsJack Reynolds
Edgar Phone #: ###-####- final ok
Final9/4/20189/5/20189/5/2018AFAIL
DetailsJack Reynolds
Please call ahead for access - Edwin Phone #: ###-####- need to seal line set penetration- need UV protection on line set- need a drip leg installed on gas line- b vent in crawl needs 3 " clearances to supply duct insulation- need to install 2 co detectors