Permit Information
Permit NumberMEC18-04305
StatusFinaled
Name ADVANCED HEATING & COOLING
Site Address 2108 N 20TH ST
Project Name 
Customer Number49521
ePlanReviewNo
Description
Alteration or Repair: Mini-Split
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/24/201810/25/201810/25/2018PPASS
DetailsBen Livingston
Please call Bow at ###-#### when in route Phone #: ###-#### Inspection requested via web by Sabrina DeHority
Final10/22/201810/23/201810/23/2018AFAIL
DetailsBen Livingston
Please call Bow Angemi at ###-#### when in route -also ask for access code-Phone #: ###-#### Inspection requested via web by Sabrina DeHority
armaflex needs uv protection
Final10/22/201810/23/201810/22/2018ACANC
DetailsBen Livingston
Please call Robin at ###-#### when in route Phone #: ###-#### >> Inspection requested via web by Sabrina DeHority Inspection cancelled from web by: Sabrina DeHority
Rough-in9/14/20189/17/20189/17/2018PPASS
DetailsBen Livingston
Please all Eric D at ###-#### to coordinate. Phone #: ###-#### Inspection requested via web by Sabrina DeHority
Rough-in9/14/20189/14/20189/14/2018PFAIL
DetailsBen Livingston
Call Eric D at ###-#### to coordinate Phone #: ###-#### Inspection requested via web by Sabrina DeHority
nothing was done to flex on the ground
Rough-in9/12/20189/13/20189/13/2018PFAIL
DetailsBen Livingston
Please call Robin at ###-#### when in route - Robin needs at least a 30 minute notice so she can meet you there. Phone #: ###-#### Inspection requested via web by Sabrina
DeHority
duct still not 4" off ground in crawl
Rough-in9/5/20189/6/20189/6/2018AFAIL
DetailsChad Schwendiman
Please call Eric D at ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Sabrina DeHority -
1) Permit description needs to show installation of mini split, not replacement of mini split.
2) Need to add exhaust fans and dryer duct to permit.
3) Missing nail plate on dryer duct.
4) Need to seal and insulate ductwork in attic.
5) Need to support ducts up a minimum of 4" off the ground in the crawl
Final8/31/20189/6/20189/5/2018ACANC
DetailsBen Livingston
Please call Robin at ###-#### when you are in route so she can meet you over there. Phone #: ###-#### >> Inspection requested via web by Sabrina DeHority Inspection cancelled from web by: Sabrina DeHority