Final | 11/25/2018 | 11/26/2018 | 11/26/2018 | A | PASS |
Brian Scoles
|
|
|
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak- final ok
|
Rough-in | 9/13/2018 | 9/13/2018 | 9/13/2018 | P | CANC |
Brian Scoles
|
|
|
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Cherva- passed already
|
Rough-in | 9/12/2018 | 9/12/2018 | 9/12/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I ok- need to seal dryer duct where penetrstes dryer box by final
|
Rough-in | 9/10/2018 | 9/11/2018 | 9/11/2018 | P | FAIL |
Brian Scoles
|
|
|
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak- crawl needs completed- b vent insulation shield on water heater needs to go all the way to roof- missing firecaulk on fireplace flue big hole on bottom- 6" fresh air can not come from roof- dryer vent needs supported every 4 feet and seal where penetrates into dryer box in wall- need to fix all rips and tears on arma flex on lineset- reinspection fee issued-( same ongoing correction on house R/I inspections)
|
Pressure Test | 9/10/2018 | 9/11/2018 | 9/11/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass
|