Final | 11/28/2018 | 11/28/2018 | 11/28/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey- final ok
|
Final | 11/26/2018 | 11/27/2018 | 11/27/2018 | A | FAIL |
Brian Scoles
|
|
|
Garage code 4053 Phone #: ###-#### Inspection requested via web by Aaron Toomey- need sediment trap installed between shut off valve and furnace in garage- need to seal gas penetration where enters crawl space at meter location- need to insulate R/A bare metal atop filter box
|
Rough-in | 9/10/2018 | 9/10/2018 | 9/10/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey- R/I ok - need to fix all rips and tears on lineset in crawl by final
|
Rough-in | 9/6/2018 | 9/7/2018 | 9/7/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey- dryer vent exterior needs to be sealed/rodent proof- need to mastic all boots to floor 1st floor- line set needs to be ran at R/I- is 6" fresh air right size for square footage didnt see anything noted on manual J- need to fire caulk b vent in chase 2nd floor at floor and ceiling- need to seal dryer vent where it penetrates into box in laundry room- left correction notice front window
|
Pressure Test | 9/6/2018 | 9/7/2018 | 9/7/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey- 20lb gas pass
|