Permit NumberMEC18-04425
StatusFinaled
Name DIAMOND HEATING AND COOLING
Site Address 3701 W CRESCENT RIM DR Unit: 107
Project NameRimcrest #107
Customer Number15484495
ePlanReviewNo
Description
Alteration: installed 2 fire inline dust smoke detectors and 11 supply dampers and 1 register
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/30/20191/30/20191/30/2019PPASS
DetailsJack Reynolds
PLEASE CALL STAN THE PROPERTY MANAGER WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery
- final ok
- no card onsite to sign
Final10/25/201810/26/201810/26/2018PCANC
DetailsJack Reynolds
please call Alex one of our technicians 30-40 mins ahead so he can meet you onsite for witnessed test. If at all possible, can this be end of day, 3-5p type time frame? If at all possible this would be appreciated, that way I can have the correct person there to meet you and have this all taken care of. Any questions or problems, call Steve at Diamond- ###-#### Phone #: ###-#### Inspection requested via web by Rick Montgomery
Rough-in10/26/201810/26/201810/26/2018PPASS
DetailsJack Reynolds
please call Alex one of our technicians 30-40 mins ahead so he can meet you onsite for witnessed test. If at all possible, can this be end of day, 3-5p type time frame? If at all possible this would be appreciated, that way I can have the correct person there to meet you and have this all taken care of. Any questions or problems, call Steve at Diamond- ###-#### Phone #: ###-#### Inspection requested via web by Rick Montgomery
-R/I ok smoke detectors installed per manuf spec and tested- ok for finish cover- will need to see access doors installed and trim finished for final
Final10/24/201810/25/201810/25/2018ACANC
DetailsJack Reynolds
PLEASE CALL SAM OUR LEAD WHEN 30-45 MINS OUT SO HE CAN MEET YOU ONSITE AND PERFORM WITNESSED TEST Phone #: ###-#### >> Inspection requested via web by Rick Montgomery Inspection cancelled from web by: Rick Montgomery
Rough-in10/5/201810/5/201810/5/2018PPART
DetailsJack Reynolds
Talked with Zach today about getting a partial R/I for cover so they can move foward with sheet rock. Zach said they would leave the ceiling open around the hvac units so that diamond havc can access the smoke detectors for testing and re mounting- Talked with Dave the building inspector and he said he was fine with a partial on the mechanical permit
Pressure Test10/1/201810/1/201810/1/2018PNR
DetailsJack Reynolds
please call Owen 30-40 mins when out so he can meet you onsite to perform test needed for you to witness. Phone #: ###-#### Inspection requested via web by Rick Montgomery- pressure differentional at smoke detector fail - talking with Owen they are going to try mounting the smoke detectors on the outside of the duct and apply the proper sampling tube and retest pressure- manufactures spec states a pressure differential of at least .01 - 1.2
Conference9/27/20189/27/20189/27/2018PDONE
DetailsJack Reynolds
smoke detector installation- talked with general about leaving the smoke detector in place and testing air requirments through the smoke detectors to make sure they meet manufactures specs
Rough-in9/24/20189/25/20189/25/2018PFAIL
DetailsJack Reynolds
Call Stan prior to going by there ###-####
- Need to provide test evidence that there enough air flow across the smoke detector in it current postion or install the smoke detector in a conventional way on the outside of the duct work so the sample tubes are in the air stream. You will also have to install fire rated access doors in the ceiling next to the smoke detectors
Rough-in9/24/20189/24/20189/24/2018ACANC
DetailsJack Reynolds
Call Stan prior to going by there ###-#### Chad S.
Final9/11/20189/12/20189/12/2018APASS
DetailsJack Reynolds
PLEASE CALL ZACH THE PROJECT MANAGER WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery- all fusible link dampers ok- 2 smoke detectors ok- ok for cover