Final | 11/16/2018 | 11/16/2018 | 11/16/2018 | P | PASS |
Brian Scoles
|
|
|
Final mechanical inspection needed if you have any questions contact Karl ###-#### thank you. I have sent the air balance report to Brian with the city of Boise Phone #: ###-#### Inspection requested via web by Karl Hestekin- final ok- airbalance ok- no card onsite to sign
|
Card not on site to sign | 11/16/2018 | 11/16/2018 | 11/16/2018 | A | PASS |
Brian Scoles
|
|
|
Final mechanical inspection needed if you have any questions contact Karl ###-#### thank you. I have sent the air balance report to Brian with the city of Boise Phone #: ###-#### Inspection requested via web by Karl Hestekin- NO CARD ONSITE TO SIGN
|
Final | 11/5/2018 | 11/6/2018 | 11/6/2018 | A | PART |
Brian Scoles
|
|
|
Mechanical Final needed for Lifetime AM preferred if you have any questions contact Karl at ###-#### Phone #: ###-#### Inspection requested via web by Karl Hestekin- need air balance report on EF 2 part of CO detection system- grid ceiling registers and flex all good- ok to cover- need relief damper completed and operational- need RTU 1E condensate drain installed- temp occupancy
|
Rough-in | 10/12/2018 | 10/15/2018 | 10/15/2018 | P | PASS |
Brian Scoles
|
|
|
PM inspection needed for Lifetime if you have any questions or concerns please contact Karl at ###-#### thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- Seal on duct ok- ok to insulate- ok to cover hard lids in bathrooms- ok for grid- need to attach this permit to right building permit
|