Permit Information
Permit NumberMEC18-04719
StatusFinaled
Name FM INC
Site Address 11522 W FAIRVIEW AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Furnish Unit heaters t stats roof flashing flue caps
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/27/201811/28/201811/28/2018APASS
DetailsBrian Scoles
Contact is Kenny ###-#### Phone #: ###-#### Inspection requested via web by Jamie Scibior- final ok- card signed
Final11/20/201811/21/201811/21/2018AFAIL
DetailsBrian Scoles
Contact Owner Randy ###-#### for access Phone #: ###-#### Inspection requested via web by Jamie Scibior- needs shut off valve ahead of regulator and sediment trap installed before regulator- needs test port after regulator and a union installed for removal of regulator for maintenence 409.5.1 IFGC
Pressure Test10/12/201810/15/201810/15/2018APASS
DetailsBrian Scoles
Contact en @ ###-#### Phone #: ###-#### Inspection requested via web by Jamie Scibior- 60lb gas pass- need sediment traps between shut off valves and appliance at final
Pressure Test10/8/201810/9/201810/9/2018AFAIL
DetailsBrian Scoles
Please contact Ken at ###-#### for information on pressure test. Phone #: ###-#### Inspection requested via web by Jamie Scibior- gauge wont zero out- please install temp shutoff valve before gauge so can be used at pressure rather than draining whole system
Pressure Test10/1/201810/2/201810/2/2018AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Jamie Scibior- gauge at 49 psi- need inert tape on gas line where penetrates into building- sediment traps need to be installed between gas shut off and appliance- b vent needs insulation shields around pipe at ceiling with minimum clearnce of 1" and stubs down 2" below insulation