Final | 2/28/2019 | 2/28/2019 | 2/28/2019 | A | PASS |
Brian Scoles
|
|
|
final ok
|
Conference | 2/27/2019 | 2/28/2019 | 2/28/2019 | A | PASS |
Brian Scoles
|
|
|
duct blast witness at 11 am- ###-####- final ok- duct blast test pass both units
|
Rough-in | 2/27/2019 | 2/27/2019 | 2/27/2019 | P | CANC |
Brian Scoles
|
|
|
blast test // Lakota Phone #: ###-####- rescheduled for tomorrow at 11 am per phone call with Brian
|
Final | 2/22/2019 | 2/25/2019 | 2/25/2019 | A | FAIL |
Brian Scoles
|
|
|
Doris- ###-####- need to witness duct blast test both units- need approved manual j onsite- need air balance report- need to support fluing in garage- condenser for one unit needs completed not set and uv protection on line set- need to fix all rips and tears in arma flex in garage both units-
|
Final | 2/22/2019 | 2/22/2019 | 2/22/2019 | P | FAIL |
Brian Scoles
|
|
|
Doris Phone #: ###-####- no access- needs garage codes or home needs to be unlocked
|
Rough-in | 11/21/2018 | 11/21/2018 | 11/21/2018 | P | PASS |
Brian Scoles
|
|
|
Locoda Phone #: ###-####- R/I ok both units
|
Rough-in | 11/19/2018 | 11/20/2018 | 11/20/2018 | P | FAIL |
Brian Scoles
|
|
|
Doris Ann Phone #: ###-####- range ducting both units still not addressed- talk to Terek about this by phone- got a plan to fix
|
Pressure Test | 11/19/2018 | 11/20/2018 | 11/20/2018 | P | CANC |
Brian Scoles
|
|
|
Doris Ann Phone #: ###-####- both units have passed pressure test
|
Rough-in | 11/8/2018 | 11/9/2018 | 11/9/2018 | A | FAIL |
Brian Scoles
|
|
|
toe kick is connect to the fantech , crawl space // Dorthy Phone #: ###-####- corrections still not addressed on range ducting- remove oval 90 degree and 6" 90 thats smashed at ceiling and reroute both units
|
Rough-in | 11/6/2018 | 11/6/2018 | 11/6/2018 | P | FAIL |
Brian Scoles
|
|
|
Dorthy Phone #: ###-####- range hood ducting correction not made (IRC 1503.1)- remove crimped oval 90 degree and smashed 6" 90 degree and reroute both units- reinspection fee issued
|
Pressure Test | 11/6/2018 | 11/6/2018 | 11/6/2018 | P | CANC |
Brian Scoles
|
|
|
Dorthy Phone #: ###-####- already passed
|
Rough-in | 10/17/2018 | 10/18/2018 | 10/18/2018 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- corrections still need to be made on fresh air and range ducting
|
Pressure Test | 10/17/2018 | 10/18/2018 | 10/18/2018 | A | CANC |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- already passed
|
Rough-in | 10/10/2018 | 10/10/2018 | 10/10/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- 6" frersh air can not come from return air can (both units)- range hood duct needs to be smooth wall (IRC M1503.1) interior surface- need to seal R/A plenum boxes in garage by final (both units)
|
Pressure Test | 10/10/2018 | 10/10/2018 | 10/10/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- 20lb gas pass both units
|