Final | 1/31/2019 | 1/31/2019 | 1/31/2019 | P | PASS |
Jack Reynolds
|
|
|
Balancing and Duct blast was completed and reports are on-site. Items referenced in previous inspection were corrected. Phone #: ###-#### Inspection requested via web by Lynn Johnston - final ok
|
Final | 1/25/2019 | 1/28/2019 | 1/28/2019 | P | FAIL |
Jack Reynolds
|
|
|
Code- 1234 Phone #: ###-#### Inspection requested via web by Lynn Johnston - need duct blast report and air balance docs onsite for review - both water heater and furnace need sediment traps installed on gas line - water heater flue needs at least three screw installed at joints
|
Rough-in | 11/9/2018 | 11/9/2018 | 11/9/2018 | P | PASS |
Jack Reynolds
|
|
|
Crawl space is complete Other notated items have been remedied Phone #: ###-#### Inspection requested via web by Lynn Johnston R/I ok- check insulaion in crawl at final
|
Rough-in | 11/5/2018 | 11/5/2018 | 11/5/2018 | P | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Lynn Johnston - Man J needs tto be approved by the city and stamped - crawl is not finished - side wall supply run in bathroom upstairs needs to be ducted out of cabinet area and looks to be blocked by water lines coming through floor
|
Pressure Test | 11/5/2018 | 11/5/2018 | 11/5/2018 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Lynn Johnston- 20lb gas pressure test ok- 5lb flue pressure test ok
|