Final | 12/5/2018 | 12/5/2018 | 12/5/2018 | A | PASS |
Brian Scoles
|
|
|
After 10 if possible. Than k you. BJ 2085730755 Inspection requested via web by william kerwin- final ok card signed
|
Final | 11/30/2018 | 11/30/2018 | 11/30/2018 | P | PART |
Brian Scoles
|
|
|
Bj 2085730755 Inspection requested via web by william kerwin- need to add shut off valve to RTU 2 on gas line- b vent for fireplace needs clearance to combustibles in exposed area and is white paint high temp rated thats painted on pipe?- need equipment set and exhaust hooked up and air balance onsite- temp occupancy ok
|
Rough-in | 11/21/2018 | 11/21/2018 | 11/21/2018 | A | PASS |
Brian Scoles
|
|
|
seal on duct ok- ok for ceiling tiles- need clearance to roofing on b vent on roof- need to secure all gas piping- need sediment trap between shut off valve and regulators on roof by final
|
Final | 11/20/2018 | 11/20/2018 | 11/20/2018 | P | PART |
Brian Scoles
|
|
|
Ceiling grid inspection. Inspection requested via web by william kerwin- all ducts above grid ceiling need sealed dont see any on it
|
Rough-in | 10/23/2018 | 10/23/2018 | 10/23/2018 | P | PART |
Brian Scoles
|
|
|
Bj 5730755 Inspection requested via web by william kerwin- R/I ok- ok to cover- RFI written and addressed for exhaust duct in wall- recall in inspection when all duct is installed
|
Rough-in | 10/18/2018 | 10/18/2018 | 10/18/2018 | P | FAIL |
Chad Schwendiman
|
|
|
Bj 5730755 Inspection requested via web by william kerwin - Exhaust systems not installed per approved plans. Need engineers approval for changes
|
Pressure Test | 10/18/2018 | 10/18/2018 | 10/18/2018 | P | PASS |
Chad Schwendiman
|
|
|
Bj 5730755 Inspection requested via web by william kerwin - 20lb gas pass for piping from roof to fireplace, 60lb gas pass from meter to roof top units
|
Rough-in | 10/17/2018 | 10/17/2018 | 10/17/2018 | P | FAIL |
Brian Scoles
|
|
|
Bj 5730755 cover inspection for the walls and hardlids Inspection requested via web by william kerwin- need approved prints on site to do inspection
|
Pressure Test | 10/17/2018 | 10/17/2018 | 10/17/2018 | P | FAIL |
Brian Scoles
|
|
|
Bj 5730755 Inspection requested via web by william kerwin- gauge below 60
|