Permit NumberMEC18-05007
StatusFinaled
Name EVENFLO HEATING & AIR CONDITIONING
Site Address 9964 W OVERLAND RD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Complete hvac
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/5/201812/5/201812/5/2018APASS
DetailsBrian Scoles
After 10 if possible. Than k you. BJ 2085730755 Inspection requested via web by william kerwin- final ok card signed
Final11/30/201811/30/201811/30/2018PPART
DetailsBrian Scoles
Bj 2085730755 Inspection requested via web by william kerwin- need to add shut off valve to RTU 2 on gas line- b vent for fireplace needs clearance to combustibles in exposed area and is white paint high temp rated thats painted on pipe?- need equipment set and exhaust hooked up and air balance onsite- temp occupancy ok
Rough-in11/21/201811/21/201811/21/2018APASS
DetailsBrian Scoles
seal on duct ok- ok for ceiling tiles- need clearance to roofing on b vent on roof- need to secure all gas piping- need sediment trap between shut off valve and regulators on roof by final
Final11/20/201811/20/201811/20/2018PPART
DetailsBrian Scoles
Ceiling grid inspection. Inspection requested via web by william kerwin- all ducts above grid ceiling need sealed dont see any on it
Rough-in10/23/201810/23/201810/23/2018PPART
DetailsBrian Scoles
Bj 5730755 Inspection requested via web by william kerwin- R/I ok- ok to cover- RFI written and addressed for exhaust duct in wall- recall in inspection when all duct is installed
Rough-in10/18/201810/18/201810/18/2018PFAIL
DetailsChad Schwendiman
Bj 5730755 Inspection requested via web by william kerwin - Exhaust systems not installed per approved plans. Need engineers approval for changes
Pressure Test10/18/201810/18/201810/18/2018PPASS
DetailsChad Schwendiman
Bj 5730755 Inspection requested via web by william kerwin - 20lb gas pass for piping from roof to fireplace, 60lb gas pass from meter to roof top units
Rough-in10/17/201810/17/201810/17/2018PFAIL
DetailsBrian Scoles
Bj 5730755 cover inspection for the walls and hardlids Inspection requested via web by william kerwin- need approved prints on site to do inspection
Pressure Test10/17/201810/17/201810/17/2018PFAIL
DetailsBrian Scoles
Bj 5730755 Inspection requested via web by william kerwin- gauge below 60