Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberMEC18-05127
StatusExpired
Name ACTION HEATING & COOLING
Site Address 7150 W TARGEE ST
Project Name 
Customer Number229573
ePlanReviewNo
Description
Alteration: Add gas furnace and gas line.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Mec-Aging Inspection12/2/201912/2/201912/2/2019 CANC
DetailsBrian Scoles
DOC - Permit Expired12/2/201912/2/201912/2/2019APASS
DetailsBrian Scoles
no calls- no activity- permit expired
Mec-Aging Inspection9/2/20199/2/20199/3/2019 FAIL
DetailsBrian Scoles
contractor needs to schedule inspection and make all corrections noted- permit will expire next aging if no activity
Mec-Aging Inspection6/3/20196/3/20196/3/2019 FAIL
DetailsBrian Scoles
needs called in for final inspection if works complete and all noted items on pressure test inspection notes need addressed
Pressure Test11/2/201811/2/201811/2/2018PPASS
DetailsJack Reynolds
Inspection requested via web by Brad Knapton
- 20lb gas pressure test ok- need to see a sediment trap after shut off at furnace- need to add duct work in crawl to permit- secondary drain at indoor coil needs a wet switch and need to see primary condensate termination point at final