Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberMEC18-05290
StatusFinaled
Name INTEGRITY HEATING & AIR LLC
Site Address 4427 W ALPINE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: Install new complete HVAC in new residential construction home with gas piping
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/29/20195/30/20195/30/2019PPASS
DetailsJack Reynolds
garage code 1234 Phone #: ###-#### Inspection requested via web by Terek Worley
- final ok
Conference5/29/20195/30/20195/30/2019PPASS
DetailsJack Reynolds
witness Duct blast test please Phone #: ###-#### Inspection requested via web by Terek Worley
- duct blast ok
Final2/11/20192/12/20192/12/2019PFAIL
DetailsJack Reynolds
garage code 1234 Phone #: ###-#### Inspection requested via web by Terek Worley
- need to witness duct blast test
- need access to furnace in attic
Rough-in1/7/20191/7/20191/7/2019PCANC
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Terek Worley
Rough-in12/14/201812/17/201812/17/2018APASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Terek Worley
- R/I ok
Rough-in12/13/201812/14/201812/14/2018AFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Terek Worley
- two range hoods will be under 400 cfm each hood has a max 190 cfm
- Man J doesnt match what is installed in home. - the Man J shows gas furnace and there is a electric furnace installed
Rough-in12/4/201812/5/201812/5/2018AFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Terek Worley
- need approved man J onsite
- two range hoods being installed either need to bring fresh air into space or provide manufacture specs showing hoods will be under 400 cfm
- need to access furnace when approved man J shows up onsite
Pressure Test12/4/201812/5/201812/5/2018ACANC
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Terek Worley
Rough-in11/20/201811/26/201811/26/2018AFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Terek Worley
- need approved Man J. onsite
- fresh air needs to come off return at furnace not return register can
- if range hood is over 400 cfm it will need make- up air. Looks like two hoods are being installed
Pressure Test11/20/201811/26/201811/26/2018ACANC
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Terek Worley- not sure what needs a pressure test. looks like furnace is electric and i dont see a gas line anywhere