Final | 1/8/2019 | 1/8/2019 | 1/8/2019 | P | PASS |
Jack Reynolds
|
|
|
We will extend flue this morning, electrician added disconnect yesterday, we will verify! Inspection requested via web by Floyd Floyd - final ok - no card to sign onsite
|
Final | 1/4/2019 | 1/4/2019 | 1/4/2019 | P | FAIL |
Jack Reynolds
|
|
|
I will make sure it''s unlocked! Inspection requested via web by Floyd Floyd Peek - A/C needs a service disconnect on roof - fresh air needs to be 10' away or exhaust needs to be 3 ' above air intake
|
Rough-in | 12/28/2018 | 12/28/2018 | 12/28/2018 | P | PASS |
Jack Reynolds
|
|
|
Need ok to cover ceiling. Inspection requested via web by Floyd Floyd Peek - R/I ok ceiling cover ok
|
Rough-in | 12/12/2018 | 12/12/2018 | 12/12/2018 | P | PASS |
Jack Reynolds
|
|
|
Partial above grid, duct work is wrapped Inspection requested via web by Floyd Floyd Peek - duct work insulation ok
|
Rough-in | 12/3/2018 | 12/3/2018 | 12/3/2018 | P | PART |
Jack Reynolds
|
|
|
Inspection requested via web by Floyd Floyd Peek - duct seal ok- ok for insulation cover - eng stated it was ok to pipe the combustion air out of mech room and into the warhouse - exhaust fan in bathroom ok
|
Rough-in | 11/26/2018 | 11/27/2018 | 11/27/2018 | A | NR |
Jack Reynolds
|
|
|
Anytime will be fine Inspection requested via web by Floyd Floyd Peek- need to make sure furnace vent is a two pipe set up- bathroom exhaust needs to be finished- install all duct work and schedule inspection for duct seal before insulation is installed
|