Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMEC18-05844
StatusFinaled
Name IDAHO GEOTHERMAL
Site Address 4281 N FOREST MEADOW AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: Complete HVAC for new home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/28/20196/28/20196/28/2019PPASS
DetailsBrian Scoles
Mike ###-####
code 0555 Phone #: ###-#### Inspection requested via web by Bryan Palmer
Final6/24/20196/25/20196/25/2019PFAIL
DetailsBrian Scoles
Mike - ###-####
Code:0555 Phone #: ###-#### Inspection requested via web by Bryan Palmer- need uv protection on mini split condenser outside- supply register doesnt fit in boot garage entry
Rough-in2/19/20192/20/20192/20/2019APASS
DetailsBrian Scoles
Mike Phone #: ###-####- R/i ok
Rough-in2/11/20192/11/20192/11/2019PFAIL
DetailsBrian Scoles
Mike Phone #: ###-####- csst gas piping needs supported/secured per manu unstallation- need approved manual j onsite- need to seal dryer duct to termination box- linsets both units need supported every 6 feet and all rips and tears fixed- mini split condensate shall be 3/4" and not poly tubing- floor boot in laundry room is to buig needs top be size of register boot- left correction notice front window of garage
Rough-in2/6/20192/6/20192/6/2019PCANC
DetailsBrian Scoles
Mike Phone #: ###-####- per phone call with mike- will reschedule
Rough-in1/9/20191/9/20191/9/2019PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Bryan Palmer
1) need approved manual J onsite for inspection
2) csst gas piping needs secure/supported per manufactires installation instructions and gas piping into fireplace will need completed when set
3) exhaust fans need hooked up none set yet
4) crawl needs completed on R/I and boots mastic to floor
5) line set needs supported every 6 feet in wall and in attic and all rips and tears need fixed
6) furnace/water heater closet needs combustion air provided for them both
5)
Pressure Test1/9/20191/9/20191/9/2019PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Bryan Palmer- 20lb gas pass