Permit Information
Permit NumberMEC19-00053
StatusFinaled
Name ARCTIC AIR INC
Site Address 1697 S FEDERAL WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair:
Alteration or Repair: Replace furnaces and A/C''s in all 4 units - apts 101, 102, 103, 104
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/4/20192/5/20192/5/2019PPASS
DetailsJack Reynolds
Inspection requested via web by Konrad Swartz
- final ok
Final2/4/20192/5/20192/4/2019ACANC
DetailsJack Reynolds
>> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
Final2/1/20192/4/20192/4/2019APART
DetailsJack Reynolds
Inspection requested via web by Konrad Swartz
- upstairs units had access- need to finish filling out duct blast stickers upstairs- still need access to units downstairs- dyrer vent done by other needs finished
Conference1/31/20192/1/20192/1/2019APASS
DetailsJack Reynolds
Duct Blast Inspection requested via web by Konrad Swartz
-all units duct blast ok
Rough-in1/24/20191/25/20191/25/2019APASS
DetailsJack Reynolds
Rough in and Duct Blast 9:30 Inspection requested via web by Konrad Swartz
- R/I ok
- unit 102 duct blast ok
- air balance will be ready to check for final
Rough-in1/23/20191/23/20191/23/2019PPART
DetailsJack Reynolds
Inspection requested via web by Konrad Swartz
- Man J needs to be stamped by the city and onsite
- range hood vent needs to be smooth walled pipe
- dryer vent needs to be installed for common laundry room and needs a backdraft damper

Final1/14/20191/16/20191/16/2019ACANC
DetailsJack Reynolds
The Builder and Property Manager are requesting 8:30 to 10:30 AM as these are occupied >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
Final1/8/20191/9/20191/9/2019PFAIL
DetailsJack Reynolds
Property Manager is requesting 3 pm for both buildings Inspection requested via web by Konrad Swartz
- need man J stamped and approved onsite
- need to add bathroom exhaust fan and duct work to permit
- linesets need UV protection
- condensate lines need extended down to ground from the 2nd floor