Final | 3/5/2019 | 3/6/2019 | 3/6/2019 | A | PASS |
Chad Schwendiman
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart
|
Rough-in | 1/21/2019 | 1/22/2019 | 1/22/2019 | A | PASS |
Brian Scoles
|
|
|
re inspection code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- R/I ok
|
Pressure Test | 1/21/2019 | 1/22/2019 | 1/22/2019 | A | PASS |
Brian Scoles
|
|
|
re inspection code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass
|
Rough-in | 1/18/2019 | 1/18/2019 | 1/18/2019 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- gas test below 20psi- need to insulate supply duct in attic above master bedroom bare metal showing- need to seal all exhaust fan hook ups from fan to metal duct- need to seal range duct completely at ceiling level in kitchen open holes in square to round- condensate drain needs nail plate at ceiling in laundry- attic all good furnace and coil match man j- left correction notice front window
|
Pressure Test | 1/18/2019 | 1/18/2019 | 1/18/2019 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- gauge below 20psi
|
Pressure Test | 1/18/2019 | 1/22/2019 | 1/18/2019 | A | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Randy Hart Inspection cancelled from web by: Randy Hart
|