Final | 9/25/2019 | 9/25/2019 | 9/25/2019 | P | PASS |
Jack Reynolds
|
|
|
garage will be open. code 1234 Phone #: ###-#### Inspection requested via web by Oleg Chervak - final ok
|
Mec-Aging Inspection | 8/27/2019 | 8/27/2019 | 8/27/2019 | | DONE |
Jack Reynolds
|
|
|
WIP
|
Rough-in | 2/20/2019 | 2/20/2019 | 2/20/2019 | P | PASS |
Jack Reynolds
|
|
|
Oleg Phone #: ###-#### - exhaust vent ok - R/I ok
|
Rough-in | 2/5/2019 | 2/5/2019 | 2/5/2019 | P | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak
|
Rough-in | 1/30/2019 | 1/30/2019 | 1/30/2019 | P | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak - Man J doesn't match the equipment thats installed - dryer vent ok - line set support ok
|
Rough-in | 1/27/2019 | 1/28/2019 | 1/28/2019 | P | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak - corrections have not been made - reschedule when corrections have been fixed
|
Rough-in | 1/17/2019 | 1/18/2019 | 1/18/2019 | P | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak - Man J needs to be approved by the city and onsite - line sets need support in the attic and insulation needs fixed - dryer vent and box on the west side needs to be installed in a 2x6 wall. Termination box has a 1/2" sticking out of the wall
|
Pressure Test | 1/17/2019 | 1/18/2019 | 1/18/2019 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak 3- 5lb flue pressure test ok 20lb gas pressure test ok
|