Final | 3/29/2019 | 3/29/2019 | 3/29/2019 | P | PASS |
Troy James
|
|
|
Francisco will be the contact ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Debbie Marino
|
Rough-in | 2/26/2019 | 2/27/2019 | 2/27/2019 | A | PART |
Jack Reynolds
|
|
|
rough in inspection for the mechanical room wall. Francisco is your contact Phone #: ###-#### Inspection requested via web by Kim Adams - bathroom and mechanical/ IT room cover ok - still need to see insulation sheild on all unit heaters
|
Rough-in | 2/21/2019 | 2/21/2019 | 2/21/2019 | P | FAIL |
Jack Reynolds
|
|
|
Rough in ; Francisco is your contact Phone #: ###-#### Inspection requested via web by Kim Adams - unit heaters need insulation sheild installed to maintain 1" clearances on b vent through roof - line set for mini split needs installed - condensate line for mini split needs installed (talked with general about location ) - bathroom exhaust fan ok for hard lid cover
|