Final | 9/12/2019 | 9/13/2019 | 9/13/2019 | A | PASS |
Jack Reynolds
|
|
|
Call prior to going Phone #: 2088718789 >> Inspection requested via mobile web by Albert - final ok - occ card not onsite to sign
|
Card not on site to sign | 9/13/2019 | 9/13/2019 | 9/13/2019 | A | PASS |
Jack Reynolds
|
|
|
Call prior to going Phone #: 2088718789 >> Inspection requested via mobile web by Albert
|
Final | 9/11/2019 | 9/12/2019 | 9/12/2019 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: 2088718789 >> Inspection requested via mobile web by Albert - need acess to roof to check corrections - make up air duct needs corrections made still - looks like a plumbing permit should be pulled aswell
|
Pressure Test | 8/26/2019 | 8/27/2019 | 8/27/2019 | A | PASS |
Jack Reynolds
|
|
|
Albert Phone #: ###-#### - 60lb gas pressure test ok - tagged meter location
|
Pressure Test | 8/22/2019 | 8/23/2019 | 8/23/2019 | A | FAIL |
Jack Reynolds
|
|
|
Albert Phone #: ###-#### - gauge was under 60 lb
|
Rough-in | 8/9/2019 | 8/12/2019 | 8/12/2019 | A | FAIL |
Jack Reynolds
|
|
|
albert Phone #: ###-#### - right side wall has combustibles within 18" of hood - all 3 exhaust fans needs extensions installed -pressure test needs to be 60lb -gas lines on roof need sediment traps and test ports - roof caps need sealed -make up air duct needs insulated and installed per prints -need to see electrical permit pulled - equipment needs to be 6" inside hood - seams on backside and left side of hood need sealed
|
Rough-in | 2/11/2019 | 2/12/2019 | 2/12/2019 | A | FAIL |
Jack Reynolds
|
|
|
Call prior to going Phone #: 2088718789 >> Inspection requested via mobile web by Albert - light tested single weld at hood and grease duct connection - need to see city approved plans onsite
|
Rough-in | 2/4/2019 | 2/5/2019 | 2/5/2019 | A | PART |
Jack Reynolds
|
|
|
Call prior to going Phone #: 2088718789 >> Inspection requested via mobile web by Albert - light test on 6' grease duct ok - still need to see approved plans from the city
|
Conference | 1/27/2019 | 1/28/2019 | 1/28/2019 | A | DONE |
Jack Reynolds
|
|
|
Call prior to going Phone #: 2088718789 >> Inspection requested via mobile web by Albert - talked with Albert about grease duct clearances on new 12' hood - also talked with him about an approved set of drawings reviewed and stamped by the city onsite
|
Conference | 1/24/2019 | 1/25/2019 | 1/25/2019 | A | CANC |
Jack Reynolds
|
|
|
Call prior to going Phone #: 2088718789 >> Inspection requested via mobile web by Albert
|